PULSAFEEDER MB9300-9600 Series Controllers
|
|
The MB9200 Series Controller is a microprocessor based controller for boiler systems.
The controller provides the ability to accurately control the level of dissolved
solids based on µS/cm on a timed, held or continuous sample basis. Select models
provide the ability to control the alkalinity of system water in units of pH.
Control Functions:
All continuously monitored sensor input functions (conductivity) will provide user
definable set points for maintaining a specific value within the system for up to
two boilers at the same time. Each set point will have a user definable differential
as the control band, programmable high and low alarm points.
Chemical Feed Timer:
The chemical feed timer shall be user selectable as any one of the following:
- Percent - User will be able to select a percent "ON" time of a user defined "cycle"
time.
- Limit - Timer will run as controller bleeds until a user programmed "limit" time
is met or the bleed is satisfied.
- Percent of Post-Bleed - Timer will run for a user defined percentage of the bleed
time after bleed is is satisfied with a fail-safe user set maximum run time.
- Pulse Timer - Timer initiated from dry contacting head water meter. User can define
timer run time, water meter input and contact accumulation before timer initiation.
- Cycle Timer - User will be able to cycle chemical on and off a specified number
of times during during a 28 day-per-month calendar basis.
- Slave Timer - Timer will turn on its output when one or more selected relays activate.
The relays can be slaved in any combination.
- Disabled - Timer can be totally deactivated.
Remote Communications :
The controller shall have the optional capability of serial communications using
PULSAworks software. The serial communications can occur either by direct RS232
port, or remotely via an optional internal modem. PULSAworks allows the user to
access real-time system values and download data history files and save files to
disk. History files may be viewed and printed in table or graph form, the graph
form can be user customized. The optional internal modem allows the controller to
perform alarm call back for alarm condition notification to a pager or computer
running PULSAworks software.
|
|
|
Pulsafeeder MB9300-9600 Series Controllers
|
For complete pricing information and material availability,
contact
us.